Safety and degradation

Controlling worse is acceptable. Not controlling at all, or silently hanging, is not. Every degradation is explicit, annunciated, and reversible.

Every outgoing value passes core/safety.py at the command boundary: setpoints are clamped to the device’s min/max including the frost floor, calibration offsets to the device’s calibration range, valve percentages to 0..valve_max_opening. The hull is the second guard: the calibration math keeps its own intermediate clamps for bit-exact debuggability. But the hull owns the boundary, and no write path may bypass it, including the valve close on an OFF intent.

Safety-relevant writes (OFF for an open window or absent heat demand, frost-floor rewrites, closing the valve) also bypass the write budget: safety is never throttled.

stateDiagram-v2
    OPTIMAL --> SENSOR_FALLBACK: room sensor lost (~2 min debounce)
    SENSOR_FALLBACK --> HOLD: no TRV temperature usable either (~2 min)
    OPTIMAL --> HOLD: room sensor and TRV temperatures lost together (~2 min)
    HOLD --> SENSOR_FALLBACK: TRV temperatures back (~5 min stability)
    SENSOR_FALLBACK --> OPTIMAL: room sensor back (~5 min stability)
    HOLD --> OPTIMAL: room sensor back (~5 min stability)

The ladder does not have to pass through SENSOR_FALLBACK. It commits to the rung the observation supports for the whole window, so losing the room sensor and every TRV temperature at once goes straight to HOLD, and a returning room sensor lifts HOLD straight to OPTIMAL.

  • OPTIMAL — the external room sensor delivers; the control law works as configured.
  • SENSOR_FALLBACK — the room sensor is unavailable, but at least one reachable TRV reports an internal temperature: calibration substitutes the mean of the TRV-internal readings. Controlling on a hot-valve sensor is worse than on a room sensor, but strictly better than controlling on a silently stale reading. A stored reading only counts while its TRV is actually reachable, and going unavailable invalidates it, so pre-outage values cannot pass as live.
  • HOLD — neither the room sensor nor any TRV temperature is usable (for example during a Zigbee outage). The kernel emits the same heating intent as on every rung, with the user’s target as the setpoint; the shell reads the rung and withholds calibration (no offsets, no valve percentages), so the setpoint reaches the device uncalibrated: the controller stops adjusting, each device stays locked on the last known target (re-sent if the device loses it), and the frost floor stays enforced on every write. Nothing downstream of the HOLD decision may re-introduce an adjustment, boost included. The only valve write on HOLD is the overheat-safe close: an OFF intent (room switched off, open window, no heat demand) closes the valve to 0 % on a direct-valve TRV whose valve BT drives, by a calibration mode that writes the valve or by boost. A room switched off turns its devices off on HOLD as on every other rung: the last known target is not locked in, and a TRV without an OFF mode receives its minimum setpoint.

Downgrades are debounced (down_debounce_seconds, 120 s) so a flapping sensor does not flip behavior; upgrades require sustained recovery (up_stability_seconds, 300 s). A sensor that stops reporting produces no events, so a periodic ladder tick (LADDER_TICK_S, 60 s) evaluates the ladder in every configuration, and a rung commits at most one tick after its window has elapsed. The rung is visible as the control_mode attribute, along with degraded_for_seconds and unavailable_sensors; entering degraded mode raises a repair issue that clears itself on recovery.

Per-TRV, the bulkhead is the kernel’s address filter: a dead TRV receives no intent (unless boost heating is active) and its native thermostat keeps controlling at the last commanded state, effectively in passthrough mode, while the other TRVs stay fully controlled.

core/watchdog.py answers one question: did a control cycle complete recently? The heartbeat is stamped on every deliberate outcome of a cycle, including skipping an unavailable TRV or deferring a write to the budget, while error paths that bail out leave it alone. The reconciler tick reads it: a device that diverges from the intent while no cycle has completed for 15 minutes is a silent hang, which raises an error and forces a cycle. A room whose devices hold the intent has nothing for a cycle to do, so a loop that stays quiet there is not reported, however long ago its last cycle ran. A running cycle holds the reconciler off, so the tick also checks how long the current cycle has been running: one that has not ended 15 minutes after it began is logged as an error once. Valve maintenance holds the reconciler off on purpose and is not counted.

Self-healing applies where the pathology is unambiguous; everything else is annunciation only:

Pathology Reaction Threshold anchor
Non-finite values in learned state Discard state, relearn from live data none needed (NaN/Inf)
Runaway auto-tuned gains (PID) Reset gains to defaults configured gain ranges
Wound-up integrator (PID) Reset integrator actuator-derived integrator limits
Oscillating output Annunciate only ≥4 reversals between ≥20-point swings in the last 10 outputs

Oscillation triggers no automatic gain backoff: a detector that backs gains off on a false positive thrashes the controller, which is worse than the oscillation it reacts to. Backoff stays a manual decision until the detector is validated against the calibration benchmark. Every verdict lands per TRV in the calibrator_health attribute; a healthy verdict clears only the grades its reporter owns, so the sanitize path and the oscillation watcher cannot flap each other’s annunciations.

Persisted state is hardened at three layers: deserialization skips a wrong-typed field individually while a non-finite value resets the whole stored entry to its defaults, an unreadable store yields defaults instead of killing startup, and the sanitize step heals whatever still reaches a controller. For a reset entry and an unreadable store, load attempts to copy the stored payload aside before the defaults apply. If that copy cannot be confirmed on disk, the defaults still apply, but saves are held back and the copy is retried, so the live store keeps the payload until the copy exists (see Persistence).