Target temperature not taken

Better Thermostat raises this repair issue when one of its TRVs keeps reporting a different target temperature from the one Better Thermostat writes to it. The issue names the TRV, the target temperature Better Thermostat wants and the one the TRV reports, as of the latest control cycle. The TRV is also listed in the thermostat’s errors attribute, so the device_error device trigger and the device error blueprint fire for it.

A write that gets lost on the radio is not an error. Better Thermostat compares the target temperature the TRV reports with the one it wants on every control cycle and writes it again when they differ. A difference of up to one step of the TRV is treated as taken, because some devices round a written value onto their own grid.

When the TRV does not take the value, the second write follows after the normal 30 seconds between writes (ten minutes for a HomematicIP head), and every further one waits twice as long as the one before, up to one hour. The issue is raised when the TRV still does not hold the value after six writes in a row. At the 30 second interval the waits are 30 seconds, 1, 2, 4 and 8 minutes, so the issue appears about a quarter of an hour after the first write. A HomematicIP head waits 10, 20 and 40 minutes and then one hour twice, so its issue appears a little over three hours after the first write. The waits keep doubling after that until they reach one hour, and from then on Better Thermostat writes the target temperature once an hour. When you change the room’s target temperature, the next write goes out at the normal pace.

  • The TRV has a setpoint limit of its own that is lower than the maximum it publishes to Home Assistant. Some calibration modes ask a TRV for a target temperature well above the room’s target, up to its published maximum, and the TRV refuses or caps it. In Zigbee2MQTT, check settings such as max_heat_setpoint_limit and min_heat_setpoint_limit.
  • The TRV is in a mode or preset in which it ignores target temperatures, for example a schedule or programme mode.
  • The TRV lost its radio connection, or its battery is low.
  1. Open the TRV’s device page in Home Assistant and compare its target temperature with the one named in the issue.
  2. If the TRV holds a lower value than asked for, raise its own setpoint limit to at least the maximum it publishes.
  3. Make sure the TRV is in a manual or heating mode in which it follows the target temperature it is sent.
  4. Check the battery and the radio connection.

The issue clears on its own, and the TRV leaves the errors attribute, as soon as the TRV reports the target temperature Better Thermostat wants or the last one it wrote.