# Actions and conditions

> The actions Better Thermostat adds to Home Assistant, their fields, and the device conditions it offers in automations.

Source: https://better-thermostat.org/setup/actions-and-conditions/

Better Thermostat adds three actions of its own and two device conditions. Everything else, such as setting a target or a preset, goes through Home Assistant's `climate` actions, which every Better Thermostat accepts.

## Actions

Each action targets one or more Better Thermostat climate entities. You find them under **Developer tools → Actions** and in the automation editor under **Add action → Better Thermostat**.

### `better_thermostat.reset_heating_power`

Sets the heating power the thermostat has learned back to its starting value. The thermostat then learns it again from the next heating cycles; the current value is published in the `heating_power` attribute and the heating power sensor.

Use it after a change that makes the learned value wrong, such as a new radiator or a room sensor in a new place.

This action takes no fields.

```yaml
action: better_thermostat.reset_heating_power
target:
  entity_id: climate.living_room
```

### `better_thermostat.run_valve_maintenance`

Runs the valve maintenance cycle now instead of at its next scheduled time: each valve is opened and closed so it does not get stuck. Only valves with valve maintenance enabled in the thermostat's settings take part.

The action fails with a message when no valve of the thermostat has maintenance enabled, or when a maintenance run is already in progress.

The action returns once the run has finished. If the thermostat is reloaded, disabled or deleted meanwhile, the run stops, puts each TRV back as it was before, and the action returns without an error.

This action takes no fields.

```yaml
action: better_thermostat.run_valve_maintenance
target:
  entity_id: climate.living_room
```

### `better_thermostat.reset_pid_learnings`

Clears everything the PID controller has learned for this thermostat, for every TRV and every target temperature. Without further fields the controller starts again from its built-in gains.

| Field | Required | Description |
| --- | --- | --- |
| `apply_pid_defaults` | no | When `true`, writes starting gains for the current target and the targets 0.5 °C above and below it, on every TRV. Default `false`. |
| `defaults_kp` | no | Proportional gain to write, 0 to 1000. Without it the built-in 60 is used. |
| `defaults_ki` | no | Integral gain to write, 0 to 2. Without it the built-in 0.01 is used. |
| `defaults_kd` | no | Derivative gain to write, 0 to 10000. Without it the built-in 2000 is used. |

The three gain fields only take effect together with `apply_pid_defaults`. With `apply_pid_defaults` the thermostat needs a target temperature; without one the action fails and nothing is reset. The PID numbers on the device show the new gains as soon as the action has run.

```yaml
action: better_thermostat.reset_pid_learnings
target:
  entity_id: climate.living_room
data:
  apply_pid_defaults: true
  defaults_kp: 40
```

## Device conditions

In the automation editor, **Add condition → Device**, a Better Thermostat device offers two conditions.

| Condition type | True while | Values |
| --- | --- | --- |
| `is_hvac_mode` | The thermostat is in the chosen HVAC mode. | `off`, `heat`, `heat_cool` |
| `is_hvac_action` | The thermostat's current action is the chosen one. | `off`, `heating`, `cooling`, `idle` |

The mode is what the thermostat is set to; the action is what it is doing right now. A thermostat set to `heat` reports `idle` while the room is warm enough. A thermostat reports `cooling` only when a cooler is configured.

```yaml
condition: device
device_id: 0123456789abcdef0123456789abcdef
domain: better_thermostat
entity_id: climate.living_room
type: is_hvac_action
hvac_action: heating
```

The device triggers are described with the blueprints that use them, in [How device triggers work](https://better-thermostat.org/setup/automation-blueprints/#how-device-triggers-work).